Introduction

Due to their specialized function—housing energy intensive IT equipment and 24/7/365 operations—data center facilities often consume over 100 (10 to 50 per floor space1) times the quantity of electricity of a similarly sized commercial office space. With such large electricity usage, the implementation of effective energy conservation measures in data centers can substantially reduce energy consumption and the associated utility costs. A thorough and detailed analysis of all energy saving opportunities should be made to ensure that the data center's total cost of operation is minimized.

As energy efficient data center designs and operational standards continue to evolve rapidly within the industry, legacy data center operators need guidance as to what good practices they should consider in order to maximize energy efficiency in their facilities.

Benchmarking Data Center Energy Performance

To improve data center energy efficiency, a baseline of current energy efficiency must be determined to measure against future performance. Power Usage Effectiveness (PUE) is a metric, originally developed by The Green Grid, that is an industry accepted measurement of data center efficiency:

PUE = Total Data Center Energy Consumption / IT Equipment Energy Consumption

Direct monitoring/metering of electric current and voltage at various critical locations in the data center will provide the data used to calculate the PUE. Because the IT equipment and total facility electric consumption will vary based upon IT equipment power demand as well as the cooling load due to local weather conditions, PUE should be calculated at frequent intervals. The PUE values can then be integrated to provide a measurement of the “average” energy performance of the data center over a defined duration of time. Energy performance changes can then be tracked to monitor the impact of implemented energy conservation measures.

Industry Energy Efficiency Resources

ASHRAE Technical Committee 9.9Mission Critical Facilities, Data Centers, Technology Spaces and Electronic Equipment produces, as part of the ASHRAE Datacom Series, several regularly updated publications that detail the current industry practices on a variety of data center design, operation, and maintenance issues. ASHRAE publications of particular interest, for data center operators to reference regarding energy efficiency, include Best Practices for Datacom Energy Efficiency and Green Tips for Data Centers.

ASHRAE also produces Standard 90.4 – Energy Standard for Data Centers which details energy efficiency requirements for the design, construction, operation, and maintenance of data centers. This standard was developed to be code-ready and to be adopted by local jurisdictions to establish guidelines for the design and construction of new data center facilities.

Energy Efficiency Opportunities for Existing Data Centers

While industry guidelines and standards identify opportunities to implement energy savings measures in newly constructed data centers or those currently being designed, what measures can an operator of a legacy data center explore to achieve greater facility energy efficiency? While not an exhaustive list, opportunities to be considered include the following:

Install Energy Usage Monitoring Equipment

Legacy data centers may lack the robust energy usage monitoring instrumentation and sensors necessary to comply with ASHRAE standards and to gather the measurements to calculate the data center PUE. Installation of energy monitoring components and systems to measure the energy efficiency of the data center are essential to effectively implement all other energy conservation measures.

Optimize Supply Air Temperatures

Adjust (increase) HVAC supply air temperatures to create an IT equipment environment consistent with the higher end of the recommended temperature ranges noted in ASHRAE Thermal Guidelines for Data Processing Environments. The higher supply air temperatures will increase compressor efficiency if a DX type unit is utilized for cooling or will increase the efficiency of the chiller plant if chilled-water air handling units are utilized for cooling.

Optimize CRAC Controls

Stand-alone computer room air-conditioning (CRAC) units utilized in legacy data centers often have individual controls and set-points that result in units running excessively as a consequence of “fighting” each other over temperature and humidity adjustments. Widening of the dead-band for the temperature and humidity settings will reduce the tendency for these units to behave in such a way. More sophisticated control scenarios can be considered to provide additional energy savings.

Separate Hold and Cold Air

Create a hot-aisle/cold-aisle layout for IT equipment to maximize the cool air flow to equipment intakes and the removal of warm discharge air from the equipment racks. Creation of the hot-aisles or cold- aisles can be accomplished through the addition of partitions or ceilings to eliminate the mixing of hot air and cold air.

Improve Underfloor Air Pressure Management

For data centers with raised floor plenums, ensuring that the raised floor system is properly sealed and that unnecessary underfloor blockages are removed will improve energy efficiency. Uncontrolled air leakage from the raised floor can result in inadequate quantities of cooled air reaching the IT equipment. Underfloor blockages and obstructions can also cause inadequate cool air flows to the equipment. These conditions necessitate higher HVAC supply air temperatures and additional fan energy to handle the equipment cooling loads.

Improve CRAC Unit Efficiency

Improvements in the energy efficiency of CRAC units, including the use of variable-speed control for supply air fans and the use of electronically commutated (EC) motors, are standard features in new CRAC units. Retrofitting existing CRAC units or replacing older CRAC units with these features will provide energy savings.

Improve Transformer Efficiencies

For data center facilities that contain older electrical distribution components that are nearing the end of their expected useful life, cost-effective energy savings can be obtained by replacing existing standard efficiency electrical transformers with high-efficiency transformers. In addition to incurring lower internal electrical losses, the high-efficiency transformers produce less waste heat that needs to be mechanically cooled. At the time of replacement, re-configuring the facility power distribution system to reduce the number of transformers needed, if practical, can also yield energy savings.

Improve Lighting Efficiency

For facilities that are currently illuminated with fluorescent lamped light fixtures, replacement or retrofitting to LED type fixtures will provide significant energy savings. Installation of enhanced lighting controls such as occupancy/motion sensors or additional manual controls to allow for lights to be shut off when spaces are vacant can also be cost-effective energy savings measures.

Conclusion

Operators of legacy data centers can reduce the total cost of operations in their facilities by integrating energy savings opportunities such as those described above. The projected savings and costs for each opportunity should be closely evaluated to determine which measures are most cost-effective, with financial resources allocated accordingly. As with all retrofit projects, considerations should include flexibility to accommodate possible future changes in technology as well as business operating conditions.

Acknowledgments

We would like to thank Keith Madigan, PE, BEAP, BCxP, LEED AP (BD+C, O+M) for providing insight and expertise that greatly assisted in this research.

Keith Madigan is a Vice President in J.S. Held's Equipment Consulting Practice. He is a licensed professional engineer with over 30 years’ experience in providing building and infrastructure design, construction management, and consulting services for clients in the private and public sectors. His experience includes assignments in construction management support, multi-discipline property condition assessments, building code consulting, and LEED/green building consulting. Keith’s assignments have additionally included construction defect investigations, building envelope evaluations, MEP commissioning, and forensic investigations/expert witness support for insurance and legal clients.

Keith can be reached at [email protected] or +1 667 239 2271.

References

  1. Energy.gov. Data Centers and Servers. https://www.energy.gov/eere/buildings/data-centers-and-servers
Find your expert.

This publication is for educational and general information purposes only. It may contain errors and is provided as is. It is not intended as specific advice, legal, or otherwise. Opinions and views are not necessarily those of J.S. Held or its affiliates and it should not be presumed that J.S. Held subscribes to any particular method, interpretation, or analysis merely because it appears in this publication. We disclaim any representation and/or warranty regarding the accuracy, timeliness, quality, or applicability of any of the contents. You should not act, or fail to act, in reliance on this publication and we disclaim all liability in respect to such actions or failure to act. We assume no responsibility for information contained in this publication and disclaim all liability and damages in respect to such information. This publication is not a substitute for competent legal advice. The content herein may be updated or otherwise modified without notice.

noun_Download_747989_000000 Created with Sketch. Download PDF
You May Also Be Interested In
White Papers & Research Reports

The Microburst Wind Potential Index: Applications for Post-Storm Surveys and Forensic Reviews

Applications and advantages of the highly adaptable microburst wind potential index (MWPI) to different storm modes in different environments and geographies....

Perspectives

The Winds of Change: Navigating Offshore Wind Disputes

This article discusses the new risks facing the relatively young offshore wind industry and proposed solutions....

Perspectives

Forensic Meteorology in Insurance: How Do Certified Consulting Meteorologists Help with Storm Damage Claims & Disputes?

An overview of the role of forensic meteorologists when consulting on storm damage-related claims and common real-world scenarios....

 
INDUSTRY INSIGHTS
Keep up with the latest research and announcements from our team.
Our Experts